Power Factor (PF) is a value that tells how much of the electricity flowing into a factory is actually put to work. The Power Factor Charge is the money that PEA (Provincial Electricity Authority) and MEA (Metropolitan Electricity Authority) collect from factories in customer types 3 · 4 · 5 when the month's maximum kvar (lagging side) exceeds a set proportion of the maximum kW in the same month. Only the excess is charged, at a flat rate per kilovar. It can be reduced with a capacitor bank that has an automatic controller.
The thresholds and rates in this article are those of PEA and MEA from the September 2026 billing month onward, excluding VAT.
| Item | Value |
|---|---|
| Trigger: month's maximum kvar (lagging side) exceeds what share of the same month's maximum kW | Above 61.97% of maximum kW |
| Rate applied to excess kilovar, after rounding the kilovar fraction (THB per kilovar, before VAT) | 56.07 THB/kvar |
| Power Factor value used on site to compare against the threshold (approximate equivalent, not a figure in the tariff notice) | 0.85 |
| Factories within scope | Types 3 · 4 · 5, both PEA and MEA |
What is Power Factor, and why does the utility charge money for it?
Power Factor is the ratio between the power that does actual work (kW) and the total power the system has to deliver (kVA). It ranges from zero to one, and the closer to one the better, because the system needs less current to deliver the same real power. The money the utility collects comes from the burden its lines and transformers carry for "the part of the electricity that does no work", not from the units of electricity the factory uses.
The electricity a factory draws from the utility has two parts mixed together. The first is real power (kW), which turns machines, gives light and gives heat. The second is reactive power (kvar), which does no visible work but must be present to build the magnetic field in motors and transformers. Combining these two at right angles gives apparent power (kVA), the total size of the electricity the lines have to deliver. Power Factor is kW divided by kVA. So the kW figure on the bill says how hard the factory works, kvar says how much non-working electricity it draws, and kVA is not the figure used for billing.
The table below is a calculated example: the same workload at 100 kW, but as Power Factor falls, the system has to deliver more kVA to achieve the same work. This example is calculated from kVA = kW ÷ PF and is not a value measured at a real factory.
| Power Factor in the example | kVA the system must deliver (calculated example, same load in every row) |
|---|---|
| 0.70 | 142.9 kVA |
| 0.80 | 125.0 kVA |
| 0.95 | 105.3 kVA |
| 1.00 | 100.0 kVA |
This extra kVA does not go anywhere. The current that carries it must run through the utility's lines, transformers and equipment just like the electricity actually used. The utility therefore has to size its equipment larger and absorb more losses in the system. The money collected when a factory draws kvar beyond the limit is the charge for this burden. Some people call it a "PF penalty", which is not the official name; the name used on the bill is Power Factor Charge.
The loads that push kvar up are inductive loads: motors, transformers, machinery, chillers, fans, pumps and air-conditioning systems. Factories with many of these are more likely to see this line.
✗ Low Power Factor wastes units of electricity, so you get charged for it
✓ For the same work (kW), low PF means more current must be drawn, not more units (kWh). The money on this line comes from the burden the utility's lines and transformers must carry, not from the units used.
Which factories are within scope of the charge?
Factories in types 3 · 4 · 5 under both PEA and MEA, and only for lagging Power Factor, which is the side produced by motors and inductive loads.
On the PEA side, this clause is written to apply to customers who are billed a demand charge, which among factories means types 3 · 4 · 5. MEA has the same clause in its tariff documents for types 3 · 4 · 5. The differences between these three types are explained in How do type 3, 4 and 5 electricity tariffs differ?
If you are not sure which type your factory is in, you can check by size, because customer type is measured by maximum power demand, not by kind of business (read how to find your own type). Small business (type 2) is the group whose power demand is below 30 kW, and neither utility applies the Power Factor Charge to this group. Once maximum power demand reaches that level or higher, the factory falls into type 3 or above and comes within scope of the Power Factor Charge.
- Lagging
- The side of Power Factor that arises when a factory draws kvar from inductive loads such as motors and transformers. The opposite is the leading side, which arises when too much compensation is applied with capacitors. The Power Factor Charge applies only to the lagging side.
When is it charged, and how much?
Every billing month, the utility compares the month's maximum kvar against the same month's maximum kW. Both are the maximum values of the billing month and need not occur at the same time. For factories within scope, if the maximum kvar exceeds 61.97% of the maximum kW, the excess is charged at a flat rate per kilovar. If it does not exceed, that month has no such line.
The ceiling is therefore not a fixed number but a proportion of that month's maximum kW. In a month when maximum kW rises, the kvar ceiling moves up with it; in a month when maximum kW falls, the ceiling shrinks. The comparison starts afresh every billing month, which is why this line can appear in some months and vanish in others.
The threshold in the tariff notice is written as a ratio of kvar to kW, not as a Power Factor value, but this ratio can be converted to a PF value. People on site therefore use an approximate equivalent PF of 0.85 as a reference point. If the PF on the factory's meter or reports sits below this level, there is a chance of seeing this line on the bill.
Ft is a separate item on the bill and is charged every month according to units used; it is a different item from the Power Factor Charge (What is the Ft rate? (in Thai))
- Find the month's maximum kW, using the highest value of the whole month
- Find the ceiling: multiply the month's maximum kW by 61.97% to get that month's kvar ceiling. If the maximum kvar does not exceed this ceiling, that month has no Power Factor Charge line
- Subtract the ceiling from the month's maximum kvar to get the excess kilovar
- Round the kilovar fraction first (below half a kilovar is dropped; half and above counts as one kilovar), then multiply the excess kilovar by the rate of 56.07 THB/kvar, which is a flat rate in THB per kilovar. This gives the pre-VAT amount of this line, and the same amount is the money that disappears if the excess is removed entirely
✗ The Power Factor Charge is calculated from the number of units used, like the energy charge
✓ It is calculated from the maximum kvar in excess of the ceiling, and the ceiling is a proportion of that month's maximum kW. Units (kWh) are not in the formula.
✗ The tariff notice sets the threshold as a minimum Power Factor value
✓ The notice writes the threshold as a ratio of maximum kvar to maximum kW. The PF value used for comparison is one that people on site have converted for convenience; it is not a figure in the notice.
How can the Power Factor Charge be reduced, and what needs to be installed?
The main fix is to install a capacitor bank with an automatic Power Factor controller (APFC) and contactors that switch steps in and out according to load, to raise the lagging-side PF until the Power Factor Charge line shrinks or disappears. What this reduces is this line only, not the demand charge.
Installation work the installer should carry out in order:
- Review current data from the meter: kW · kvar and PF
- Log load data continuously, day and night, to see when PF is low
- Calculate the capacitor size required (kvar)
- Check harmonics if the factory has VFDs, inverters or electronic loads
- Select and install an APFC/capacitor bank divided into multiple steps
- Set the PF target at 0.95 to 0.99 on the lagging side
- Test and verify results at the point of common coupling with the utility (PCC)
Installing too many capacitors can also be a problem. Over-compensation flips PF to the leading side, so the APFC should switch steps according to load rather than leaving them permanently connected, and the PF target should be kept within the range set in step 6; there is no need to push it all the way to one. If the factory has high harmonics, a detuned reactor should be used together with the capacitors, and after installation the results at the PCC should be checked on an ongoing basis.
What should not be expected is a change in the demand charge line, because that line is calculated from maximum kW, not kVA, so correcting PF does not reduce it (What is the demand charge?). The measurable result is that the Power Factor Charge amount calculated in the previous section shrinks or disappears.
The capacitor size in step 3 can be estimated initially with the formula below, so that you can discuss with the installer whether the figure they propose is in a reasonable range.
- Harmonics
- Something that must be checked before installing capacitors when the factory has VFDs, inverters or electronic loads. If harmonics are high, a detuned reactor must be used together with the capacitors.
- Example: a factory has a load of 500 kW and an existing PF of 0.80 (this is the example's starting value, not the threshold at which charging begins)
- This example wants to raise PF to 0.95
- Capacitor size (kvar) = real power (kW) × (tan of the existing PF angle − tan of the target PF angle)
- Putting the example values into the formula gives roughly 210 kvar, which is an initial estimate; the actual size must be measured from on-site load data as in step 2
✗ Low Power Factor raises the demand charge because the bill is based on kVA
✓ The demand charge is calculated from maximum real power in kW, not kVA, so correcting PF does not reduce that line. It only reduces the Power Factor Charge line.
✗ The closer PF is set to one, the better
✓ Set the target in a range that does not reach one, because over-compensation flips to the leading side, and let the APFC adjust according to load.
If the factory already has solar rooftop or is about to install it
Solar reduces the kW drawn from the utility, but the kvar from motors stays the same, so Power Factor at the purchase point can fall, and if it drops below the value compared against the threshold, a Power Factor Charge can appear. Solar does not help with this. The fix is to configure the capacitor system so that it sees and accommodates the solar.
What must be set up correctly:
- Install the APFC's CT across the main incoming point, before the split to factory load and solar, or use a controller model that supports systems with renewable energy
- Set the PF target at around 0.95 on the lagging (inductive) side, not at one all the time, to leave room for solar swings so it does not cross over to the capacitive side
- Divide the capacitor bank steps into smaller sizes, so that when solar is running and kW changes slightly the system does not have to switch a large capacitor and cause a jolt
- Upgrade the APFC controller to a model that supports solar (hybrid/smart controller), which calculates compensation by looking at the direction of power flow so that over-compensation does not occur